MRV 5-RC Service Manual
SYJS-03-2019REV.A
Edition: 2019-03

Questions and Answers

  • A
    Amy LarsenSep 16, 2025
    How to fix current detecting circuit abnormal of compressor module in Haier Heat Pump?
    • J
      john01Sep 16, 2025
      If the current detecting circuit of the compressor module is abnormal in your Haier Heat Pump, replace the inverter control board with abnormal current detection loop.
  • E
    Edward HardyAug 25, 2025
    What to do if four-way valve reversing failure in Haier MRV 5-RC AB072MCERA(M)?
    • T
      Thomas BeckerAug 25, 2025
      In case of a four-way valve reversing failure in your Haier Heat Pump, the suggested solution is to have it correctly replaced by after-sales service on site and ensure the refrigerant is sufficient.
  • G
    Gary Davis DDSAug 25, 2025
    How to fix outdoor compressor discharging temperature (Td1, Td2) too high failure in Haier MRV 5-RC AB072MCERA(M)?
    • T
      Trevor AndersonAug 26, 2025
      If the outdoor compressor discharging temperature (Td1, Td2) is too high in your Haier Heat Pump, the suggested solution is to have the discharging temperature sensor replaced by after-sales personnel on site.
  • J
    Julia JohnsonAug 26, 2025
    What to do for fan motor module hardware over current in Haier MRV 5-RC AB072MCERA(M)?
    • J
      Jill LiuAug 27, 2025
      If the fan motor module in your Haier Heat Pump experiences a hardware over current issue, the solution is to replace the fan motor.
  • R
    Rachel SanchezSep 18, 2025
    What to do if radiator temp. sensor of compressor module is abnormal in Haier MRV 5-RC AB072MCERA(M) Heat Pump?
    • K
      Kimberly SmithSep 18, 2025
      If the radiator temperature sensor of the compressor module is abnormal in your Haier Heat Pump, replace the variable frequency board.
  • D
    Deborah BradleySep 23, 2025
    How to resolve AT24C04 EEPROM communication failure in Haier MRV 5-RC AB072MCERA(M)?
    • M
      Micheal PetersSep 23, 2025
      To resolve AT24C04 EEPROM communication failure, AT24C04 EEPROM data check failure, or IM EEPROM data or communication failure in your Haier Heat Pump, replace EE.
  • W
    williamsjulieSep 8, 2025
    How to fix emergency stop function switch failure in Haier MRV 5-RC AB072MCERA(M)?
    • D
      Debra JacobsSep 9, 2025
      If the emergency stop function switch fails in your Haier Heat Pump, short circuit the CN18.
  • J
    James RoseSep 9, 2025
    What to do if incorrect settings of quantity, address or capacity for outdoor unit in Haier MRV 5-RC AB072MCERA(M) Heat Pump?
    • C
      Cheryl HaleSep 9, 2025
      If there are incorrect settings of quantity, address, or capacity for the outdoor unit of your Haier Heat Pump, the suggested solution is to research and lock the outdoor unit.
  • G
    ghendricksSep 2, 2025
    What to do if discharging temperature sensor Td1 and Td2 failure in Haier MRV 5-RC AB072MCERA(M) Heat Pump?
    • P
      Phillip GarciaSep 3, 2025
      If the discharging temperature sensors Td1 and Td2 fail in your Haier Heat Pump, the solution is to have them correctly replaced by after-sales personnel on site.
  • L
    Lori HernandezSep 1, 2025
    What to do if outdoor unit compressor discharging temperature (Td1, Td2) too low failure in Haier MRV 5-RC AB072MCERA(M)?
    • H
      Heather AndersenSep 1, 2025
      If the outdoor unit compressor discharging temperature (Td1, Td2) is too low in your Haier Heat Pump, the suggested solution is to have the discharging temperature sensor replaced by after-sales personnel on site.