156
SW1 SW2 SW3 function Digital tube LD1 ~ 4 display
Outdoor
unit
address
0-3
7 0 Outdoor unit LEVa1 open degree
0---470pluse
Press START (SW5) for 2 seconds, 1111, enter the
set state: ashing, press UP (SW4) valve fully open,
according to DOWN (SW7) 2min after the valve is fully
closed; automatically exit the setting state
Press STOP (SW6) for 2 seconds, display 0000, quit
the set state, stop ashing display
8 0 Outdoor unit LEVa2 open degree
9 0 Outdoor unit LEVb open degree
10
A
0 Outdoor unit LEVc open degree
11
B
0
Outdoor unit output
electromagnetic valve
LD1
4WV
1 open 0 close――High to the left
LD2
SV1
1 open 0 close
LD3
SV3
1 open 0 close
LD4
Reserved
Display “-”
12
C
0
Outdoor unit output
electromagnetic valve
LD1
SV6
1 open 0 close――High to the left
LD2
SV9
1 open 0 close
LD3
SV10
1 open 0 close
LD4
SV11
1 open 0 close
13
D
0
Outdoor unit output
electromagnetic valve
LD1
SVX
1 open 0 close
LD2
SVY
1 open 0 close
LD3
Reserved
Display “-”
LD4
Reserved
Display “-”
14
E
0 Heating belt output
LD1
CH1
1 open 0 close
LD2
CH2
1 open 0 close
LD3
CHa
1 open 0 close
LD4
Reserved
Display “-”
15
F
0 Program version 1 representation Ver1.0
SW1 SW2 SW3 function Digital tube LD1 ~ 4 display
Outdoor
unit
address
0-3
0 1 Pd
Unit: kg, 2 decimal places
2 1 Ps
3 1 Td1
Unit: degree
4 1 Td2
5 1 Tdef
7 1 Toil1
8 1 Toil2
9 1 Toci1
14
E
1 Tsacc
15
F
1 Th
SW1 SW2 SW3 function Digital tube LD1 ~ 4 display
Outdoor
unit
address
0-3
0 15
F
Reserved
1 15
F
Tao
25 Unit: degree
2 15
F
Pd_temp
4 15
F
Ps_temp
5 15
F
Tliqsc
6 15
F
Tsco
8 15
F
Frequency conversion press INV1 running time Unit: Min
9 15
F
Frequency conversion press INV2 running time Unit: Min
10
A
15
F
Frequency conversion press INV1 current CT Unit: A, 1 decimal places
11
B
15
F
Frequency conversion press INV2 current CT Unit: A, 1 decimal places
12
C
15
F
Frequency conversion compressor INV1 DC voltage Unit: V
13
D
15
F
Frequency conversion compressor INV2 DC voltage Unit: V