Failure code
Outdoor
digital
display tube:
125-4, 5
Indoor wired
controller:
7D
Indoor unit LED status
LED5 Failure description:
Fan motor speed un-match
20 times
Outdoor unit LED status
LED1 LED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-RC series
Diagnosis Troubleshooting
2. Abnormity detection method
Check if the compressor
module is damaged
Check if the fan rotation is
smooth;
Check whether the fan
blade load is blocked;
3. Abnormity conrmation
conditions
Hall signal logic built-in the fan
motor is wrong too many times
4. Possible causes
Fan blade overload
Fan motor is bad
Y
Whether the power supply voltage is
too low or uctuating signicantly
N
Adjust the power supply.
Y
Check if the electrical box connect
correctly
Reconnect or re-fix it in
accordance with wiring
diagram.
N
Check if the inverter module is
normal
N
Replace the inverter module
Y
Exchange the left and the right
fan motor, if the failure fan motor
is OK
N
Replace fan motor