77
Specication
Model AV08NMSETA
Outdoor coil
Number of rows 2
Tube pitch (a)×row
pitch (b)
mm 19.05×22
Fin spacing mm 1.4
Fin type (code) HYDROPHILIC ALUMINIUM
Fin coating type Optional Clear lacquer
Salt spray test
duration
Hour 168
Tube outside dia.and
type
INNERGROOVE TUBE
mm Ф8
Coil length × height mm 1122×1584
Number of circuits 14
Cabinet coating
Coating type Powder coating
Salt spray test
duration
Hour 72
Sheet metal material Hot zinc plate
Sheet metal thickness mm 1.0
Control panel enclosure IP class Standard IP24
Outdoor air ow m
3
/h 10000
Outdoor sound level (sound pressure level ) dB (A) 55
Outdoor sound level (sound power level ) dB (A) 66
Outdoor unit
Dimension (W*H*D) mm 1050×400×1636
Packing (W*H*D) mm 1150×510×1790
Net weight kg 168
Gross weight kg 183
Refrigerant
Type R410A
Charged volume kg 7.4
Throttle type EXV
Design pressure MPa 4.15
Refrigerant piping
Liquid pipe mm 9.52
Gas pipe mm 19.05
Total pipe lenth m 300
Max. pipe length
(Equivalent/ Actual)
m 175/150
Max.Diff. indoor/
outdoor unit
m
50 (Outdoor higher than indoor)
40 (Indoor higher than outdoor)
Max.Diff. indoor/indoor
unit
m 15
Connectable indoor unit ratio % 50%~130%
Maximum indoor units Piece 13
Connection wiring
Power wiring mm
2
6.0
Signal wiring mm
2
Shield wire: (0.75-2)*2
Operation Range °C
Cooling: -15~43
Heating: -15~21
Norminal condition: indoor temperature (cooling): 27DB
(
°C
)
/19WB
(
°C
)
, indoor temperature (heating): 20DB
(
°C
)
/14.5
WB
(
°C
)
Outdoor temperature
(cooling): 35DB
(
°C
)
/24WB
(
°C
)
, outdoor temperature
(heating): 7DB
(
°C
)
/6WB
(
°C
)
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.

Table of Contents