7.Funcitions and Control
7.1 Main functions and control specification of indoor unit
7.1.1   Automatic operation 
When the running mode is turned to automation after starting the system, the system will first 
determine the running mode according to the current room temperature and then will run according to 
the determined mode. Tr in the following selection conditions means room temperature, Ts means 
setting temperature, Tp means temperature of indoor coil pipe       
Tr≥23
                    Choose Cooling Mode 
Tr
23                   Choose Heating Mode 
After turning to the automation mode, the running mode can be switched between cooling mode, 
fan mode and heating mode according to  the change of the indoor ambient temperature. But the 
automatic conversion between cooling mode and heating mode must be conducted after 15 minutes.
 
7.1.2   Cooling operation mode 
Temperature control range:    16 ---30
Temperature difference:  1  
* Control features: When Tr
input airflow >Ts set temperature , the compressor will be opened,
the indoor fan will operate at the set speed and the mode signal will be sent to the outdoor system. 
When
 Tr
input airflow  Ts set temperature , the compressor will be opened, the indoor fan will 
operate at the set speed and the mode signal will be sent to the outdoor system. The system will keep 
the original status if Tr= Ts. 
Airflow speed control: (temperature difference 1
) 
Automatic: When Tr≤Ts+3
, high speed. 
When Ts+1
≤Tr<Ts+3 , medium speed 
When Tr<Ts+1
, low speed 
When the sensor is off, low speed 
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 
3 minutes (remain at high speed for 3 minutes.) before the next switch. 
Manus: When the system is operating, you can set the high, medium or low speed manually. ( When 
the sensor is on or off, the system will change the speed 2 seconds after receiving the signal.) 
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting  function:  preventing  the  frosting  on  the  indoor  heat  exchanger  (when  cooling  or
dehumidifying ). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM) 
and 
the  temperature  of  the  indoor  coils  has  been  below  zero  centigrade  for  10  seconds,  the 
compressor will be stopped and the malfunction will be recorded in the malfunction list. The indoor 
system will continue to run. When the temperature of the indoor coil is raised to 7
, the compressor 
will be restarted again (the requirement of 3 minutes’ delay should be satisfied.) 
* timing system on/off function.
* Dormant control function.
Functions and Control
Domestic air conditioner