EasyManua.ls Logo

Hamilton Engineering EVO Plus Series - Annual Inspection

Hamilton Engineering EVO Plus Series
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
PART 8. MAINTENANCE
B. ANNUAL INSPECTION (See LIT91179 Maintenance Checklist for required tools and materials)
An inspection should cover, at a minimum, the following areas:
Inspect all fittings, controls and connections for leaks, damage, or fouling
Fire side:
Heat exchanger
Burner and ignitor
Burner door and rear wall insulation
Drain system components:
Hoses & clamps
Trap assembly
Condensate neutralizer
Test all safeties and operating controls
Water side temperature rise (∆T) test
INSPECTION AND CLEANING (photos illustrating each step follow sets of instructions)
CAUTION: Before removing the door of the appliance, switch o the electrical power supply to it.
Remove the front cover and check the sensors, transducers, all pipes, lines and connections, and the heat
exchanger (top, bottom) for traces of water and water leakage.
• Inspect the top of the casing and/or the top of the appliance for water leakage or traces of water from the air
supply pipe or the air vent (if applicable).

Table of Contents

Related product manuals