EasyManua.ls Logo

HANYOUNG NUX ML-D2H - Page 26

HANYOUNG NUX ML-D2H
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multi Loop Controller
24
Register
address (HEX)
Symbol
Description
Property
(R/W)
Setting range Unit Initial value
CH1 CH2
n : Number
of channel
163
(A3)
263
(107)
RHRS
Set SV change time
(hr.) at RAMP control
R/W 0 ~ 100 hour 0
164
(A4)
264
(108)
DR Set control run R/W
0: Reverse run (heating)
control
1: Direct run (cooling)
control
ABS 0
165
(A5)
265
(109)
OHL
Set high limit to
Manipulated Value
R/W 0.0 ~ 100.0 % 100.0
166
(A6)
266
(10A)
OLL
Set low limit to
Manipulated Value
R/W 0.0 ~ 100.0 % 0.0
171
(AB)
271
(10F)
BS Set input correction R/W EUS (-100 ~ 100%) EUS (0%)
172
(AC)
272
(110)
FL Set input filter R/W 0 ~ 100 ABS 0
173
(AD)
273
(111)
SVH Set SV high limit R/W EU (0 ~ 100%) EU (100%)
174
(AE)
274
(112)
SVL Set SV low limit R/W EU (0 ~ 100%) EU (0%)
175
(AF)
275
(113)
FRH Set PV high limit R/W EU (0 ~ 100%) EU (100%)
176
(B0)
276
(114)
FRL Set PV low limit R/W EU (0 ~ 100%) EU (0%)
177
(B1)
277
(115)
SLH
Set scale high limit
at DCV input setting
R/W EU (0 ~ 100%) mV EU (100%)
178
(B2)
278
(116)
SLL
Set scale low limit
at DCV input setting
R/W EU (0 ~ 100%) mV EU (0%)
179
(B3)
279
(117)
DOT Set decimal point R/W 0 ~ 3 :
decimal point digit
ABS 0
181
(B5)
281
(119)
PBC
Cooling control
Proportional band
setting
R/W EUS (0 ~ 100%) EUS (2%)
182
(B6)
282
(1A0)
TIC
Cooling control integral
time setting
R/W 1 ~ 3600 Second 240
183
(B7)
283
(1A1)
TDC
Cooling control
derivative time setting
R/W 1 ~ 3600 Second 60
184
(B8)
284
(1A2)
CTC
Cooling control control
period setting
R/W 1 ~ 100 Second
RELAY :
30 Sec.
S.S.R :
2 Sec.
185
(B9)
285
(1A3)
POC
Cooling control
Emergency output
setting
R/W 0.0 ~ 100.0 % 0
186
(BA)
286
(1A4)
HYSC
Cooling control
ON / OFF control
Hysteresis setting
R/W EUS (0 ~ 10%) EUS (0.2%)
187
(BB)
287
(1A5)
ROC
Stop cooling control.
Output setting at monitor
status
R/W 0.0 ~ 100.0 % 0
191
(BF)
291
(1A9)
HC
Heating, heating /
cooling control settings
R/W
0 : heating control
1 : heating/cooling control
ABS
0 (heating
control)
192
(C0)
292
(1AA)
HC_DB
Heating / cooling control
dead band setting
R/W -100 ~ 50 % 0

Related product manuals