27
Before staring Installation Operation Specifications
No.
0
Description
+100 +200 +300 +400
Description by channel
93 - -
- - - -
-
94 - -
- - - -
-
95 ADDR Switch address - - - - -
96 MAX_CH Number of channels - - - - -
97 R_SYS System data - - - - -
98
R_OPT Option data - - - - -
99 ROMVER Version - - - - -
3.2.4 ML-D4register description
Register address (HEX) Description
40001(0) ~ 40099(63)
CH1~4 PV, SV, MV, TSV, CHSTS, EVSTS and common channel setting
※ Please use address
40000 for Modbus
communication
40101(65) ~ 40199(C7) CH1 related setting
40201(C9) ~ 40299(12B) CH2 related setting
40301(12D) ~ 40399(18F) CH3 related setting
40401(191) ~ 40499(1F3) CH4 related setting
Register address (HEX) Symbol
Description
Property
(R/W)
Setting range Unit
Initial
value
CH1 CH2 CH3 CH4
n : Number
of channel
1(1) 2(2) 3(3) 4(4) PV
Process value
R EU(0 ~ 100%) ℃ -
6(6) 7(7) 8(8) 9(9) SV
Set value
R/W EU (0 ~ 100%) ℃ EU (0%)
11(B) 12(C) 13(D) 14(E) MV
Manipulated
Value
R 0.0 ~ 100.0 % -
16(10) 17(11) 18(12) 19(13) CHSTS
Channel
status
R
OR run for situation occurrence
15 Bit: Set “1” at System Data error
14 Bit: Set “1” at Calibration Data error
13 Bit: Set “1” at input circuit error
12 Bit: Set “1” at EEPROM error
11 Bit: Set “1” after 24 hours of auto toning (AT)
10 Bit: Set “1” at standard contact point
correction (RCJ) error
9 Bit: Set “1” when exceeding ±5% input range
8 Bit: Set “1” at input sensor error (B. OUT)
2 Bit: Set “1” at auto tuning (AT) run
1 Bit: Set “1” at monitor mode
0 Bit: Set “1” at run start
ABS -
21(15) 22(16) 23(17) 24(18) TSV
Current target
set value
R EU (0 ~ 100%) ℃ EU (0%)
26(1A) EVT_STS
Event status
R
Indication of occurrence to all events
previously set
0: no event occurred
1: event occurred
ABS -
27(1B)
EVBUS_STS
Event bus output
status
R
Event bus output OR run
7 Bit(128): Set “1” at event bus8 output occurrence
6 Bit(64): Set “1” at event bus7 output occurrence
5 Bit(32): Set “1” at event bus6 output occurrence
4 Bit(16): Set “1” at event bus5 output occurrence
3 Bit(8): Set “1” at event bus4 output occurrence
2 Bit(4): Set “1” at event bus3 output occurrence
1 Bit(2): Set “1” at event bus2 output occurrence
0 Bit(1): Set “1” at event bus1 output occurrence
ABS -
31(1F) LOCK
Parameter
setting lock
R/W
0: possible to edit all parameters
1: possible to edit only SV, R/S, AT, CHEN
parameters
2. impossible to edit all parameters
ABS 0
32(20)
COMCHK
Time setting for
RS485
communication
disconnection
detection time
R/W
0: OFF
1 ~ 3,600
second
0 (OFF)
33(21)
PARA_SAVE
Save parameter
when
communication
R/W
0: Automatic parameter save
1: save manually using PARA_COPY
parameter
ABS 0