Remote group
High limit voltage of remote input
Low limit voltage of remote input
High limit on scale
Low limit on scale
PV Filter
PV Bias
Signal Name Description Condition Initial value
Heater break alarm group
Current setting mode of HBA 1
Current setting mode of HBA 2
Hysteresis setting mode HBA 1
Hysteresis setting mode HBA 2
Current measurement value of HBA 1
Current measurement value of HBA 2
Set HBA mode
OFF / 1 ~ 50 A
OFF / 1 ~ 50 A
EUS (0.0 ~ 100.0 %)
EUS (0.0 ~ 100.0 %)
Only display
(0 ~ 50 A)
Only display
(0 ~ 50 A)
OFF
OFF
EUS
(0.5 %)
EUS
(0.5 %)
5.000
1.000
1
2
OFF
EUS
(0.0 %)
Signal Name Description Condition Initial value
REMOTE INPUT GROUP
If selecting REMOTE in Control group, set value will be set by remote set.
In remote condition, SV is changeable by front keys, but the controller is controlled by external set
value. Do not change set value by remote in auto tuning.
Set remote mode
1,000 ~ 5,000 V
but, R. INH > R. INL
Thermocouple : FR-H ~ FR-L
DC voltage : SL-H ~ SL-L
Decimal point is set by DP-P.
OFF / 1 ~ 120
EUS (-100.0 ~ 100.0 %)
HEATER BREAK ALARM GROUP
Heater break alarm group consist of output dead band and current detection display mode and
detects 2 spots (to be ordered seperately: current transformer model CTL-6-S. measurement
range : 1 ~ 50 A).
22
23
1 : Thermocouple, R.T.D input ( FR-H ), DC voltage ( SL-H )
2 : Thermocouple, R.T.D input ( FR-L ), DC voltage ( SL-L )
EUS : Range at an engineering unit in compliance with the span of an instrument.
: It is not indicated in PX7. (There is no HBA function in PX2, PX3)
Optional
Optional
27