9.5.4 Extension module HKM 2
If "Outside temperature shut-down - separated" is chosen (installer settings no.
D12), different temperatures can be set for each heat circuit.
H 7 Heat circuit 4 Day-room temperature 20° 2370
H 8 Heat circuit 4 Reduction temperature 16° 2375
Menu Description Factory: Modbus ad-
dress
H 11 HWT 3 Day clock Mo-Su ON 17:00 OFF 20:00 2380
H 11a-g HWT 3 weekly Mo/Tu/We/Th/Fr/Sa/Su ON 17:00 OFF 20:00 2385 - 2415
H 12 HWT 3 Set temperature 60°C 2420
H 12a Circulation pump HWS 3
ON 06:00 11:00
OFF 08:00 13:00
2421
H13 Heat circuit 5 day clock Mon - Sun
ON 06:00 15:00
OFF 09:00 22:00
2426
H 13a-g Heating circuit 5 weekly Mo/Tu/We/Th/Fr/Sa/Su ON 17:00 OFF 20:00 2431 - 2461
H 14 Heat circuit 5 Day-room temperature 20°C 2466
H 15 Heat circuit 5 Reduction temperature 16.0°C 2468
H 16 Heat circuit 6 day clock Mon - Sun
ON 06:00 15:00
OFF 09:00 22:00
2470
H 16a-g Heating circuit 6 weekly Mo/Tu/We/Th/Fr/Sa/Su
ON 06:00 15:00
OFF 22:00 09:00
2475 - 2505
H 17 Heat circuit 6 Day-room temperature 20.0°C 2510
H 18 Heat circuit 6 Reduction temperature 16.0°C 2512
Menu Description Factory: Modbus ad-
dress
Menu Description Factory: Modbus ad-
dress
No. 11 Heating off at outside temperature over 16° 2514
No. 11a-h
Heat circuit 1 - A and ext. HC off at outside
temperature
16° 2515 - 2522
No. 12 All heat circuits off at day reduction temp. over 8° 2523
No. 12a-g Heat circuit 1 - A off at day reduction 8° 2524 - 2530
No. 13
All heat circuits off at night reduction outs. temp.
over
-5°
2531
No. 13a-g Heat circuit 1 - A off at night reduction -5° 2532 - 2538
No. 14 Automatically fill for suction times
ON 08:00 00:00
OFF 19:00 00:00
2540
No. 14a Automatically fill for suction times
ON 07:00 14:00
OFF 19:00 00:00
2545
No. 14b Automatically fill for suction times
ON 21:00 00:00
OFF 00:00 00:00
2550
No. 15 Holiday mode not active 2555
No. 15a-g Holiday mode heat circuit 1 - A not active 2560 - 2590
No. 16 Holiday time from... - to... ---
No. 16a-g Holiday time heat circuit 1 - A from... - to... ---
No. 18a Start deashing No ---
No. 20 Date / Time ---
No. 21 Release rem. maintenance not released 2595
No. 21a
Automatically deactivate rem. maintenance
release
1 h
2600
No. 22 Heater off from... - to...
No. 30 Pellet storage 1000 kg