Technical Data
3.2 Inadmissible fuels
Fuels with water content >35%
Formation of condensate
Increased corrosion in the boiler
Paper / Cardboard
Chip boards, impregnated timber
Black coal, brown coal or lignite
Waste
Plastics
4 Execution of the boiler room
Boiler room must executed according to legislation in your country.
See "Design of the boiler room" in the installation manual
Keep the boiler's air openings free.
Do not store any flammable materials in the boiler room.
Execute the boiler room in frost-proof condition.
fireproof, plane and solid floor- and ceiling construction
In accordance with regulations, have the main heating switch installed by an
electrician (depending on building regulations).
Fire extinguisher
5 Design of the fuel storage room
Design your pellet fuel storage room in accordance with local regulations
(e.g. ÖNORM M 7137 or VDI 3464).
See "Design of the fuel storage room" in the installation manual
Only install metal fill pipes, electrically grounded and connection to atmosphere.
Pay attention to noise protection
Protection against moisture, water and dust.
Correctly position impact protection mat(s) and install slant floor.
6 Execution of heating circuits
The heating circuits must be designed correctly for optimum operation of the boiler.
Authorised heating diagrams: See heating diagrams enclosed.
The layout of the heating circuits' accumulators, pumps and mixers has to be
designed according to legislation by the installer.
D A N G E R
Danger of suffocation due to odorless carbon monoxide in the storage room
Ventilate sufficiently before entering the fuel storage room
Keep window/door open during stay
Position second person outside to supervise
Dust explosions in the storage room due to the explosive combustion of
dust (pellet dust)
Pay attention to proper grounding of the pellets transportation tubes
No motors in the fuel storage room
Except agricultural buildings
No other source of ignition (e.g. light) in the storage room
No electrical equipment (e.g. light switch) in the storage room
No welding works in dusty environment