Cleaning, Maintenance
2 Cleaning and maintenance
Boiler monitoring and cleaning intervals are based on the operation hours
and fuel quality.
Observe country-specific regulations and the inspection and sweeping inter-
vals dictated by these.
Pos. Tasks of maintenance Interval ( a = annually
a
)
a. At least once annually, at the latest after 4000 full-load hrs, 8000 partial-load hrs or after a message has appeared on the
control panel
1 Tap off the turbulators and clean the turbulator space 1x a
2 Clean flue pipe 2x a
3
Clean post-combustion chamber with poker
(visual check via inspection glass)
1x a
(as required)
4
Clean combustion chamber with poker 1 x a (as required)
5
Remove ash box and clean out the ash under the grate 1x a
6
Dismount exhaust fan and clean housing and impeller 1x a
7
Grease stoker chain and check chain tension 1x a
8
Clean pellet vacuum turbine 1x a
9
Clean the pellet vacuum turbine filter. 1x a
10
Disconnect, remove and clean the lambda sensor 1x a
11
Ash box emptying as required