13
P68 Pellet Stove
#8 Installing through the ceiling
Through the ceiling vent, follow PLvent
manufacturers recommendations when using wall
and ceiling pass through. Note: Do not place joints
within wall pass-throughs.
Fig. 14
PL vent manufacturer's
firestop spacer and
support
(See Page 6 for
corner installation
clearances)
Minimum flue vent
conguration
It is recommended that outside
air be installed with this venting
congurationtoreducesmoke
and creosote smell in the room
in the event of power failure.
Min. above ground level
18"
Storm collar
Flashing
3" min.
3" min.
12" min.
3" min.
Venting
Fig. 15
3" min.
No insulation or
other combustible
m a te r i a l s a r e
allowed within
3" of the pellet
vent pipe. Unless
specified by the
pipe manufacturer
12" min. wall to outlet
36" min clearance to any
combustible material
Fig. 16