EasyManua.ls Logo

Harman PB105 - Page 8

Harman PB105
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
3-90-07205R26_10/14
Refer to the illustration under “Parts Locations” in this
manual to identify the components listed below:
1.Installthecontrolboardcoveraswellastheaccesscover
locatedonthefeedercover.
2. Install the spring handles provided with the unit on
the ash door, firebox door and the heat exchanger
cleanoutrodhandles.(Fastenhandlesbyturningthem
counterclockwiseandpushinginwardsimultaneously).
3.Install3/4”MPTboilerdraininthettingasshown.
Note: Use pipe thread sealant or Teon tape on ALL
threads before connections are made.
4.Install3/4”MPTpressurereliefvalveasshown.
5.Installthe1/2”MPTaquastatwellinttingasshown,then
placeaquastatinthewellandfastenwithaziptie.The
aquastat sensor is located under the top sheet metal
jacket.
6.Installthe1/2”MPTtemperature/pressuregaugeintting
asshown.
7.Locateandinstalloutsideairtemperaturesensor.Location
ofthissensorshouldbeonthenorthsideofthehomeor
buildingandoutofdirectsunlight.Usethecablesupplied
withtheboilertoattachthesensortotheterminalslocated
onthehopper.(Placeatthebacksidejustaboveandto
therightofthemainpowerconnectionbox)Thewirescan
beconnectedtothesensorwiththeconnectorssupplied.
Wirenutorbuttspliceconnectorscouldalsobeused.The
connectionsattheboilercanbedonewiththetwo1/4”
femalepushonconnectorssupplied.
8. Fasten the conduit to the ash base with the clamps
provided.
Design:
Therstthingthatneedstobedoneisdecidingwhereand
howtheboilerwillbeinstalled.
Things that need to be taken into consideration are the
intendeduseoftheboilerforexample,istheboilergoingtobe
usedasyourprimaryheatingsystemorisitgoingtobeused
asasecondaryorbackupheatingsystem.Ifitistobeused
inconjunctionwithanexistingoilorgasboilersystemwillit
bepipedinparallelorinseries?Theanswerstotheseand
otherquestionscanbedeterminedbytalkingtoyourcertied
dealeroraqualiedHVACorplumbingcontractor.Thiswill
ensurethattheboilerisinstalledandpipedtoaccommodate
yourneedsandexpectations.
Consideration must be given to the venting as well as
electricalandclearancerequirements.(Clearancesmustbe
maintainedtocombustiblesandalsoforservice)
Makesurefansarenotusedinthefuelstoragearea,unless
theyareinstalledsoasnottocreateanegativepressurein
theroomwherethesolidfuelburningapplianceislocated.
Assembly
Floor Protection:
The striped area indicates the minimum required floor
protection area if the boiler is going to be placed on a
combustibleoor.Itrequires40”X55”(US)or42”X55”(CAN)
ofnoncombustibleoorprotectionasshown.16”(US)or
18”(CAN)oftheoorprotectionmustbeinfrontoftherebox
doorasshown.Floorprotectionmustbeaminimumof26
gaugesheetmetal.Floorprotectionmustalsobeprovided
underanyhorizontalrunofventpipeequaltotheoutside
diameteroftheventingplus2”toeachside.
Example: 4” type “L” or “PL” vent pipe has an outside
diameterof4-1/2”+2”oneachsideequalsaprotectedoor
areaof8-1/2”wideunderneaththehorizontalrun.
42" CANADA
18" CAN
16" USA
40" USA
55" USA & CAN
MINIMUM NON-COMBUSTIBLE FLOOR PROTECTION AREA
NON-COMBUSTIBLE
FLOOR PROTECTOR
55" USA & CAN
42" CANADA
40" USA

Related product manuals