Haskris CWS - Adjusting Alarm Set Points

Default Icon
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 9 of 12
Effective Date: 6 May 2022
Revision: 02
Adjusting Alarm Set Points
Purpose: When the CWS/CGS is in Auto mode, it will automatically switchover to city water backup
on high temperature and low flow. The high temperature alarm set point is the supply temperature
threshold at which switchover to city water backup is triggered. On units with a flow transducer, the
low flow alarm set point is the threshold at which switchover to city water backup is triggered.
1. Press on the controller
2. Press or to highlight Setpoints
3. Press to go into that menu section
4. To change an alarm set point value, press to move the blinking cursor to the value
5. Press or to adjust the value
6. Press to move the blinking cursor to the top left corner
7. With the blinking cursor in the top left corner, press or to navigate to additional alarm
set point screens (if applicable)