Do you have a question about the Haskris LX Series and is the answer not in the manual?
Some units have a green light indicating the unit's ON/OFF status.
Indicates liquid level sufficiency, or 'FULL'/'Liquid Level Low' status.
Indicates liquid temperature is above or below the alarm set points.
Indicates high refrigerant pressure or building water fault.
Indicates low refrigerant pressure, possibly due to a leak.
Periodically inspect tank for clarity and debris. Drain and replace water yearly.
Flush system for biological growth, pH change, or debris using hydrogen peroxide.
Add sodium bicarbonate to raise pH; use propylene glycol for persistent growth.
Requires potable distilled water and glycol mixture to resist freezing.
Change glycol periodically, check pH (7-10) and glycol percentage.
Clean wye strainer on return fluid connection during glycol change.
Procedure to adjust bypass pressure setting by turning an adjustment screw.
Perform checks every 2 weeks for 3 months post-installation, then 1-2 times yearly.
This document outlines the operation and maintenance procedures for Haskris LX-Series, R-Series, WW-Series, and OPC-Series units, focusing on temperature control, indicator lights, strainers, filters, drain lines, water quality, bypass pressure relief valves, refrigerant sight glass, and condenser cleaning.
Haskris units are designed to maintain precise fluid temperatures for various applications. They achieve this through different control mechanisms: ON/OFF Cycling Control, Parametric Control, and Programmable Logic Control (PLC). The units can be refrigerated or non-refrigerated, with non-refrigerated units utilizing facility water regulating valves for temperature maintenance.
The document details three types of electronic temperature controllers:
Loading...