Do you have a question about the Haskris LX Series and is the answer not in the manual?
Some units have a green light indicating the unit's ON/OFF status.
Indicates liquid level sufficiency, or 'FULL'/'Liquid Level Low' status.
Indicates liquid temperature is above or below the alarm set points.
Indicates high refrigerant pressure or building water fault.
Indicates low refrigerant pressure, possibly due to a leak.
Periodically inspect tank for clarity and debris. Drain and replace water yearly.
Flush system for biological growth, pH change, or debris using hydrogen peroxide.
Add sodium bicarbonate to raise pH; use propylene glycol for persistent growth.
Requires potable distilled water and glycol mixture to resist freezing.
Change glycol periodically, check pH (7-10) and glycol percentage.
Clean wye strainer on return fluid connection during glycol change.
Procedure to adjust bypass pressure setting by turning an adjustment screw.
Perform checks every 2 weeks for 3 months post-installation, then 1-2 times yearly.
Loading...