EasyManua.ls Logo

Haskris LX2 - User Manual

Default Icon
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Effective Date: 07 November 2022
Revision: 00
MANUAL
MODELS LX1, LX2, LX3
Question and Answer IconNeed help?

Do you have a question about the Haskris LX2 and is the answer not in the manual?

Summary

Installation

Line Sizing

Provides guidelines for sizing interconnecting piping based on flow rates and pipe length.

Startup

50;60 Hz Selection Switch

Explains how to set the switch for the correct incoming electrical frequency.

ON;OFF Switch

Describes the operation of the ON/OFF rocker switch and its role in fault resetting.

Pump Priming

Details the procedure for priming the pump if it does not self-prime upon startup.

Bypass Pressure Relief Valve

Instructions on how to adjust the bypass pressure relief valve setting for optimal flow and pressure.

Final Checks

Verifies system flow and pressure, checks for leaks, and allows for temperature stabilization.

Controller Display

Faults

How to identify, display, and understand fault descriptions and associated timestamps.

Maintenance

Overview

This document is a manual for Haskris LX1, LX2, and LX3 chiller models, providing comprehensive information on their installation, operation, maintenance, and technical specifications.

Function Description:

The Haskris LX series chillers are designed to provide controlled cooling for various applications. They circulate a fluid (typically distilled water, but some units are compatible with other fluids) to remove heat from an external system, maintaining a desired temperature. The chillers are available in air-cooled and water-cooled condenser configurations, catering to different environmental and facility requirements. They feature a controller display for monitoring and adjusting operational parameters, as well as remote communication capabilities for integration with building monitoring systems (BMS).

Important Technical Specifications:

  • Dimensions:
    • LX1 and LX2: 15" W x 32" D x 30" H (38.1cm W x 81.3cm D x 76.2cm H)
    • LX3: 19" W x 34" D x 34" H (48.3cm W x 86.4cm D x 86.4cm H)
    • Note: Custom dimensions may exist for alternative design configurations.
  • Clearances:
    • At least 6 inches (15 cm) on sides and rear for air flow.
    • At least 36 inches (91 cm) on the front for controller access.
    • Access to the top of the unit.
    • Additional clearances on sides and rear may be required for service.
  • Standard Ambient Air Temperature (for air-cooled condensers): 55°F to 90°F (13°C to 32°C).
    • Note: Some units may be customized for extended ambient temperature ranges.
  • Maximum Heat Rejection To Air (for air-cooled condensers):
    • LX1: 7,510 BTU/hr (2.2 kW)
    • LX2: 15,020 BTU/hr (4.4 kW)
    • LX3: 29,700 BTU/hr (8.7 kW)
  • Water-cooled Condenser Requirements:
    • Maximum inlet pressure: less than 100 psi (6.9 bar).
    • Minimum available differential pressure: 10 psi (0.7 bar).
    • Maximum differential pressure: 100 psi (6.9 bar).
    • Required facility water flow rate depends on the model and inlet temperature, calculated using a multiplier (LX1: 0.9, LX2: 1.3, LX3: 2.9) against a base GPM value derived from a provided chart.
  • Fluid Compatibility: Typically clean, potable distilled water. Contact Haskris for compatibility with other fluids.
  • pH Range: Acceptable range is 7 to 10.
  • Electrical: Refer to the nameplate label for detailed electrical requirements. 3-phase units include a phase monitor.

Usage Features:

  • Installation:
    • Location: Clean indoor environment. For air-cooled units, ensure compatible ambient air temperature and sufficient climate control capacity for heat rejection. For water-cooled units, confirm building water source meets temperature and flow rate requirements.
    • Piping: Comply with local codes. Use opaque 150 psi minimum rated reinforced EPDM hose for short runs; copper piping for long runs with vibration isolators. Insulate piping, label flow directions, and install isolation ball valves. For water-cooled units, an 80-mesh wye strainer at the building water inlet is recommended.
    • Line Sizing: Recommendations provided for various flow rates (8 LPM/2.1 GPM, 16 LPM/4.2 GPM, 23 LPM/6.1 GPM) based on total straight pipe length and nominal pipe size (ID). Haskris offers assistance for pipe run review and recommendations.
    • Electrical: Requires a licensed electrician for installation. Dedicated service disconnect and time-delay fusing or circuit breaker per nameplate. Units may have a power cord or require hardwiring to a terminal block.
    • Reservoir Filling: Fill with clean, potable distilled water just below the threaded neck. Have extra water available for initial startup.
  • Startup:
    • 50/60Hz Selection Switch: Some chillers have a selector switch to match incoming electrical frequency.
    • ON/OFF Switch: Rocker switch on the front. Toggling OFF then ON resets faults.
    • Pre-startup Power: Electrical power must be applied at least 12 hours before startup to energize the crankcase heater and remove liquid refrigerant from the compressor. If not possible, energize for at least 1 hour, then cycle the unit ON/OFF 3-4 times before leaving it ON.
    • Pump Priming: All fluid is removed from the pump head before shipment. The pump typically self-primes if the reservoir is full. If low pressure (<10 psi) is displayed, loosen the priming plug on the pump head to release air and a small amount of fluid, then re-tighten.
    • Bypass Pressure Relief Valve (for turbine pumps): Limits pressure by bypassing flow. Adjustment involves loosening a nut, restricting the external circuit, rotating an adjustment post with a flat head screwdriver (clockwise to increase, counterclockwise to decrease pressure), removing restriction, and repeating until desired flow/pressure is achieved. Then, tighten the nut.
    • Final Checks: Verify flow and pressure, replenish tank level as piping fills, check for leaks, and allow 15 minutes for temperature stabilization. Flush the tank if debris is present.
  • Controller Display:
    • Main Display: Shows status, set value (sv) and present value (pv) of supply fluid temperature, supply pressure, supply flow rate, and refrigerant pressures (low and high).
    • Adjusting Set Value (sv): Use the arrow buttons to move the blinking cursor to the sv, adjust the value, then move the cursor back to the top left.
    • Units of Measure: Selectable combinations: CAN (°C, psi, GPM), UK (°C, bar, IGM), USA (°F, psi, GPM), SI (°C, bar, LPM). Access through the Settings menu.
    • Status Modes: STARTUP, ON, OFF, Off by Alrm (alarm/fault), Remote OFF.
    • Faults: The "!" button flashes red when a fault occurs. Press the button to view fault descriptions, time, and date stamp. Multiple faults are indicated. Faults are reset by cycling the ON/OFF switch.
    • Fault History: View past faults even when "NO ALARMS" is displayed.
  • Remote Communication Capability:
    • Options: Alarm contacts, remote ON/OFF interlock, Modbus, BACnet.
    • Modbus and BACnet: For integration with Building Monitoring Systems (BMS). Requires a physical wire connection (3-wire RS-485 MSTP or ethernet TCP/IP) and software alignment.
    • Configuration: Access communication settings via the Service menu (password 6420). Select the communication option (BACnetIP Ethernet, ModbusIP Ethernet, BACnet RS-485, Modbus RS-485), then adjust associated settings, including IP address if applicable. Power cycle the controller for changes to take effect.

Maintenance Features:

  • Schedule: Recommended inspection every 6 to 12 months, depending on environmental and operating conditions.
  • Activity: Check cleanliness of water and electrical readings during each inspection.
  • Condenser Coils (Air-cooled units): Dust and debris can restrict airflow. Remove a side panel, use a brush to loosen debris, and vacuum to collect it.
  • Suction Strainer: Nylon strainer in the tank prevents pump damage. Check for debris or biological growth. Clean or replace if dirty. Note: Cavitation due to a dirty strainer is not covered under warranty.
  • Particle Filter: Captures debris leaving the chiller. Replace when pressure increases 5-6 psi (0.3-0.4 bar) above startup running pressure.
  • Wye Strainer (Water-cooled units): Captures debris from building water. Clean during routine maintenance or when pressure at the inlet increases 10 psi (0.7 bar) or more.
  • Liquid Level and Water Quality:
    • Liquid Level: Ensure the reservoir is full of clean water.
    • pH: Maintain pH between 7 and 10. Add sodium bicarbonate to raise pH if needed.
    • Cleanliness and Flushing: If substantial debris or biological growth is present, flush the system. This involves adding 1 pint (0.5 L) of 3% hydrogen peroxide per 15 gallons (57 L) of water (after confirming compatibility with the application), circulating for 20-30 minutes, draining, and refilling with clean, potable distilled water. Repeat as necessary.
    • Glycol: If biological growth persists, use laboratory/food grade (99% pure) propylene glycol to create a 10% mixture. Haskris recommends additives only as a last resort.

Haskris LX2 Specifications

General IconGeneral
BrandHaskris
ModelLX2
CategoryRefrigerator
LanguageEnglish

Related product manuals