Location
Locate the unit in a clean indoor environment.
For units with air-cooled condensers, confirm ambient air temperature is compatible. Confirm
the climate control system has enough spare capacity to accept heat rejection from the chiller.
Refer to the table below.
Haskris Chiller
Model
Standard Ambient
Air Temperature*
Maximum Heat
Rejection To Air
LX1
55°F to 90°F (13°C to 32°C)
7,510 BTU/hr (2.2 kW)
LX2
55°F to 90°F (13°C to 32°C)
15,020 BTU/hr (4.4 kW)
LX3
55°F to 90°F (13°C to 32°C)
29,700 BTU/hr (8.7 kW)
*Some units are designed with customizations to accommodate extended ambient temperature ranges,
contact Haskris with any questions
Air-cooled Condenser: Compatible ambient air temperature ranges and heat rejection