COMMISSIONING MANUAL
____________________________________________________________________________________
__________________________________________________________________________________
Page 10/32
SOUND2.943.001-E.e
7. MOUNTING SHIELDED CABLES
IN THE CABLE GLANDS
7.1. CABLE PREPARATION
The interfaces are connected by shielded cables. These cables pass through shielded cable
glands.
Prepare the cable like below
7.2. CABLE MOUNTING
Contact disks (D): Nickel plated brass.
The threaded connector connects the shielding braid to the earthed unit.
1
2
D
D
Cable C
Cable characteristics: (c)
Shielding: braided copper
Maximum distance: 500 m
Wire resistance: < 40 /km
Important:
The cable shielding (c) must be connected
at both ends to the corresponding terminals
for the differential voltage to be lower than
30 V
OR
up to 9.5mm