COMMISSIONING MANUAL
____________________________________________________________________________________
__________________________________________________________________________________
Page 25/32
SOUND2.943.001-E.e
14. Threshold signals
The high and low threshold signals indicate that the measured level has passed either above a critical
high value or below a critical low value.
These two limits may be independently adjusted by high level and low-level parameters in digital
outputs menu.
These signals by default are available on terminal J2 (1-2 for level high, 3-4 for level low).
Digital outputs parameters:
Function: The user can choose for any digital output a
function between Alarm lvl high, alarm lvl low, alarm user.
Output status is the actual value of the output
Map Number is the alarm number which is display in
alarm menu.
Polarity (Normal or inverse)
Value: In this case: Alarm lvl high is 80 %
Alarm
Parameters
Measures
Calibration
Cross Talk
Outputs
System