EasyManua.ls Logo

Heat Controller DMC12SB-0 - Piping Length and Elevation

Heat Controller DMC12SB-0
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service Manual 17
Piping Length And Elevation
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7meters (16.4~23.0ft).
In case more than 5m(16.4ft)
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
Pipe Size
Capacity
(Btu/h)
Suction
Evap
Max.
length
A
m(ft)
Additional Refrigerant
g/m(oz/ft)
Max.
Elevation
B m(ft)
Standard
Length
m(ft)
9k
3/8" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
1/2" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
12k 1/2" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
18k
1/2" 1/4" 7.5(25) 15(49) 30(98) 20(0.22)
5/8" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
24k 5/8" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
Installation

Related product manuals