HEATEC Firestorm - Maintenance Schedule

HEATEC Firestorm
12 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Heatec, Inc. 5200 Wilson Road Chattanooga, Tennessee 37410 www.heatec.com (423) 821-5200 (800) 235-5200 Fax (423) 821-7673
REQUIREMENT
WEEKLY
MONTHLY
QUARTERLY
YEARLY
Clean flame scanner. X
Check intake area of blower to make sure it is not blocked by foreign material and is
free from buildup of dirt.
X
During normal operation check all pressure gauges and thermometers on heater and
record any changes from previous indications.
X
Check all operating and limit controls and settings to make sure they are set properly
and are working properly.
X
Check heater and piping to ensure there are no leaks. X
Check heater to ensure there is no structural damage to heater or signs of over-
heating.
X
Check burner control linkage to make sure it is not binding or loose. X
Remove packing from inside heater and check to ensure that calcium buildup is not
excessive.
X
Check strainers to ensure they are not clogged. X
Have exhaust stack gases analyzed and have burner tuned by a specialist X
Heatec Firestorm water heaters should be checked periodically according to the requirements below. Failure
to properly maintain your heater could result in a fire or explosion.
MAINTENANCE SCHEDULE
Firestorm™ water heaters
© 2010 Heatec, Inc.
Publication 1-10-218