INSTALLATION INSTRUCTIONS Fan Coil: FMA4X, FMA4P
Specifications subject to change without notice.
496 01 8001 04
7
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in p ersonal
injury.
Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate protective clothing
and gloves when handling parts.
4.
Inspectel ectrical connections for tightness and
controls for proper operation each heating and cooling
seas
on. Service as necessary.
NOTE
: The installing technician should explain system
operation to the consumer with particular emphasis on indoor
fan
coil operation sou
nds and filter maintenance.
Table 3 – PSC
-
Airflow Performance (Standard CFM)
MODEL
FMA4P
BLOWER
SPEEDS
EXTERNAL STATIC PRESSURE (in. w.c.)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
18
High
813 775 731 692 653 609 560 501 424
Med
695 656 620 581 540 498 440 380 -
Low
603 562 525 485
443 393 - - -
24
High
947 895 847 799 753 704 655 592 530
Med
845 801 759 716 675 626
573 510 -
Low
676 640
602 563 523 499 - - -
30
High
1367 1312 1252 1192 1131 1063 990 908 821
Med
1211 1165 1114 1065 1016 960 899 833 748
Low
992 952 912 873 828
782 728 656 627
36
High
1397 1345 1290 1263 1196 1116 1051 980 907
Med
1298 1252 1198 1147 1094 1037
976 910 842
ow
1149 1105 1056 1008 960
909 856 791 726
--- Shaded boxes represent airflow outside the required 300-450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230V with no electric
heat and factory---approved filter.
2. Airflow is equivalent for front or bottom return configurati
ons.
Table 4 – ECM
-
Airflow Performance (Standard CFM)
MODEL
FMA4X
BLOWER SPEEDS
EXTERNAL STATIC PRESSURE (in w.c.)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
18
Tap (5)
Tap (4)
Tap (3)
Tap (2) - Factory
Tap (1)
24
Tap (5)
Tap (4) - Factory
Tap (3)
Tap (2)
Tap (1)
30
Tap (5)
Tap (4)
Tap (3)
Tap (2) - Factory
Tap (1)
36
Tap (5)
Tap (4) - Factory
Tap (3)
Tap (2)
Tap (1)
--- Shaded boxes represent airflow outside the required 300-450 cfm/ton.
NOTES:
1.
Airflow based upon dry coil at 230V with no electric heat and factory---approved filter. For FMA4X airflow at 208V is approximately the same as 230V because
the multi ---tap ECM motor is a constant torque motor. The torque doesn’t
drop off at the speeds in which the motor operates.
2.
Airflow is equivalent for front or bottom return configurations.
Table 5 – Filter Sizes
Unit Size Filter Size In. (mm)
18, 24
16x20x1 (406x508x25)
30, 36
20x20x1 (508x508x25)
913 881 848 818 792 763 731 691 650
825 787 753 717 682 650 617 580 540
737 700 663 630 589 550 511 474 436
675 632 596 555 521 480 440 399 366
590 548 499 455 430 368 338 309 263
913 881 848 818 792 763 731 691 650
825 787 753 717 682 650 617 580 540
737 700 663 630 589 550 511 474 436
675 632 596 555 521 480 440 399 366
590 548 499 455 430 368 338 309 263
1362 1325 1266 1238 1197 1159 1119 1080 1040
1282 1242 1176 1151 1111 1071 1028 975 936
1267 1225 1143 1120 1078 1036 993 942 897
1157 1111 1052 1016 971 929 884 84
2 802
1077 1028 965 932 886 850 804 768 732
1362 1325 1266 1238 1197 1159 1119 1080 1040
1282 1242 1176 1151 1111 1071 1028 975 936
1267 1225 1143 1120 1078 1036 993 942 897
1157 1111 1052 1016 971 929 884 842 802