7 Error Handling
36 Programmer PG 02
Error Reason
3001 ErrPickup1 Error at pickup 1
3002 ErrPickup2 Error at pickup 2
3004 ErrOverspeed Overspeedl
3031 ErrOilPressEcy Oil pressure below speed dependent shutdown threshold
3050 ErrFeedback Error at feedback of actuator 1
3051 ErrFeedback2 Error at feedback of actuator 2 (PRIAMOS III)
3052 ErrFeedback3 Error at feedback of actuator 3 (PRIAMOS III)
3056 ErrFeedbackRef Error at feedback reference of actuator 1
3059 ErrFeedbackAdjust Error at automatic actuator adjustment with actuator 1
3060 ErrFeedbackAdjust2 Error at auto. actuator adjust. with act. 2 (PRIAMOS III)
3061 ErrFeedbackAdjust3 Error at auto. actuator adjust. with act. 3 (PRIAMOS III)
3075 ErrClearFlash Error at erasing the flash memory
3076 ErrParamStore Error at saving of the parameters in flash memory
3077 ErrProgramTest Error during permanent check of programme memory
3078 ErrRAMTest Error during permanent check of RAM memory
3089 ErrWatchdog Undefined programme flow, internal programming error
3090 ErrData No parameters or check sum over parameters wrong
3091 ErrLogical Error of parameter structure
3093 ErrStack Stack overflow, internal programming error
3094 ErrIntern Exception, internal programming error
7.4 Error Parameter List
The below error parameter list contains descriptions of the causes of each single error and
of the control's response. Furthermore, it lists the appropriate actions to be taken to remove
the respective error.
The errors are stored in the volatile error memory under the parameter numbers 3000 and
higher and (as far as provided) in the permanent error memory under the parameter
numbers from 3100 onward.
The errors are sorted by ascending numbers with the parameter on the left indicating the
actual error as stored in the volatile memory and with the parameter on the right indicating
the one stored as a sentinel in the permanent error memory. As explained above, the
control will only react to actual errors whereas the permanent error memory serves no
other purpose than to accumulate information on the occurrences of errors.