INSTALLATION AND OPERATING INSTRUCTIONS
4211-70 G
Rev. 3
5/9/14
R.D. LD
DIAGRAM 1
MOUNTING BRACKET LOCATION AND MINIMUM DISTANCE TO COMBUSTIBLE MATERIAL
Recheck your distances from the
heater to combustible materials to
be sure you have the proper
minimum distances.
DIAGRAM 2
C
D
2"
1"
20 1/4"
73 1/2"
Minimum
Screws
13 3/4"
15 3/8"
B
6 1/4"
Use the long screws in the
upper holes of the mounting
bracket
A
6½"
Min.
2"
Temperat-
ure
46 3/4"
Minimum
Guard
Rail
(Upper Bench)
Floor
Area
Ceiling
Height
Volume
Cu.Ft.
Ceiling
Height
Volume
Cu.Ft.
CB PK-1
CB PK-1 to
Heater
1 208 21.6 2 # 10AWG+ GR
2 # 10AWG+ GR
1 240 18.8 2 # 10AWG+ GR
2 # 10AWG+ GR
3 208 12.5 3 # 12AWG+ GR
3 # 12AWG+ GR
3 240 10.8 3 # 12AWG+ GR
3 # 12AWG+ GR
1 208 28.8 2 # 8AWG+ GR 2 # 8AWG+ GR
1 240 25 2 # 10AWG+ GR
2 # 10AWG+ GR
3 208 16.7 3 # 12AWG+ GR
3 # 12AWG+ GR
3 240 14.4 3 # 12AWG+ GR
3 # 12AWG+ GR
1 208 38.5 2 # 8AWG+ GR 2 # 8AWG+ GR
1 240 33.3 2 # 8AWG+ GR 2 # 8AWG+ GR
3 208 22.2 3 # 10AWG+ GR
3 # 10AWG+ GR
3 240 19.2 3 # 10AWG+ GR
3 # 10AWG+ GR
WIRE SIZE
Viki 4.5
1720-45-02
4.5
VAC AMPS
HEATER MODEL /
Product Number KW
MINIMUM ROOM
12 sq. ft. 73 1/2"
21 sq. ft. 73 1/2"
100 96" 210
96" 310
250 96"
PHASE
425
6
Viki 8.0
1720-80-02
8 31 sq. ft. 73 1/2"
175
Viki 6.0
1720-60-02
Page 2
K
"A"
DISTANCE
"B"
DISTANCE
"C"
DISTANCE
"D"
DISTANCE
"K"
DISTANCE
Viki 4.5 3" 4" 4"
12 1/4" 26 1/2"
Viki 6.0 4" 5" 5"
12 1/4" 26 1/2"
Viki 8.0 5" 6" 6"
12 1/4" 26 1/2"
MINIMUM
HEATER
OBSERVING MINIMUM DISTANCES IS
REQUIRED TO REDUCE FIRE HAZARD
2"
6½"
Min.
CB PK-1
18" min
10"
max
CB PK-1
18"
min