EasyManua.ls Logo

Herrmidifier Herrtronic MD Series - Troubleshooting Without Unit-Detected Faults

Herrmidifier Herrtronic MD Series
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Herrtronic
®
MD Series
Installation, Operation, & Maintenance Manual
27
www.herrmidifier-hvac.com
Inputs / Outputs of Terminal Strips and Terminal Block
Terminal Block
Position 1-6 24 RET (GND)
7-12 24 VAC
All twelve (12) positions should be utilized if the Room Dispersion Unit (RDU) is installed
RDU Terminal Strip – Connections to RDU only
Pole
1 24 RET (GND) (Always)
2 24 VAC Trigger (24 VAC when contactor is energized)
3 Line Voltage (Always)
4 Line Voltage (Always)
5 24 VAC Air (24 VAC when switch Proving Switch is closed)
6 24 VAC (Always)
Control Terminal Strip
Pole
1 24 VAC (Always)
2 Airow / High Limit input, 24 VAC for operation
3 External “Off”, 24 VAC for operation
4 Control input ground – Modulating and on/off
5 Control input signal – Modulating and on/off
6 +5 VDC
7 +20 VDC
8 Limit input ground - Modulating
9 Limit input signal - Modulating
10 +5 VDC
11 RS-485 Communication, Negative, Digital
12 RS-485 Communication, Positive, Digital
Figure 30
Hard Water/Softened Water*
(750-1000 Micromho)
Adjust Menu Items to These Settings
MDM MDS/
MDD
Cycle Time (Menu #3) 75 115
Low Drain Threshold (Menu #2) 88 84
Capacity Setpoint (Menu #2) 96 96
High Drain Threshold (Menu #3) 108 108
*Naturally soft water is less than 50 micromho.
Figure 31
Very Hard Water
(> 1000 Micromho)
Adjust Menu Items to These Settings
MDM MDS/
MDD
Cycle Time (Menu #3) 60 100
Low Drain Threshold (Menu #2) 91 86
Capacity Setpoint (Menu #2) 94 92
High Drain Threshold (Menu #3) 105 105