TRANSPORTATION, HANDLING, INSTALLATION
40
MODEL
CABLE SECTION(AWG)
230V
CABLE SECTION(AWG)
460V
CABLE SECTION(AWG)
575V
HVD 5
4 x AWG8
4 x AWG10
4 x AWG10
HVD 7
4 x AWG8
4xAWG10
4xAWG10
HVD 11
3xAWG6+AWG8
4xAWG8
4xAWG10
HVD 15
3 x AWG3 + AWG6
4xAWG8
4xAWG8
HVD 18
3 x AWG2 + AWG6
3xAWG6+AWG8
4xAWG8
HVD 22
3 x AWG1 + AWG4
3xAWG4+AWG8
3xAWG6+AWG8
HVD 30
3 x AWG2/0 + AWG2
3XAWG3+AWG6
3XAWG6+AWG8
HVD 37
3 x AWG3/0 + AWG1
3XAWG2+AWG6
3XAWG4+AWG8
HVD 45
N/A
3 x AWG1/0 + AWG3
3 x AWG3 + AWG6
HVD 55
N/A
3 x AWG2/0 + AWG2
3 x AWG2 + AWG6
HVD 75
N/A
3 x 250 kcmil + AWG1/0
3 x AWG2/0 + AWG2
Power supply cables to be sized and installed by a qualified electrician. If different
length of power cable is required, the cross-section of the power cable may need to
be changed. In this case please contact your local service organization.