Code Parameter Name Min Max Units
Setpoint °C/°F
PS Password 0 199
/C Offset for air temp sensor -127 127 °C/°F
(in tenths of a degree: i.e. a value of “1” adds 0.1° to value)
rd Regulator differential (superheat) set point (a “0” in this field = 0.5°C or 0.5°F) 0 19 °C/°F
dI Time between defrost cycles (defrost interval) 0 199 hours
dt Defrost temperature termination set point -50 127 °C/°F
dP Max duration of defrost if using electric or hot gas defrost, or the actual 1 199 min
duration of defrost if doing timed defrost
dd Drip time 0 15 min
d8 Alarm delay after defrost 0 15 hours
d/ Defrost probe reading (read-only) °C/°F
AL Low temperature alarm differential (subtract this value from the temperature 0 127 °C/°F
set point to get low alarm temperature set point) (0 = no low temp alarming)
AH High temperature alarm differential (add this value to the temperature set 0 127 °C/°F
point to get high alarm temperature set point) (0 = no high temp alarming)
F1 Fan on at temperature set point (used if F0 = 1) -50 199 °C/°F
Fd Fan delay after defrost drip time for each F0 value 0 15 min
H5 ID code for programming key -99 +
T External parameter programming -99 199