CEA7 CONTROL UNIT ALARMS | PAGE 48
Detection of the current asymmetry alarm is congured by default (Alarms table,
parameter 255) to be activated: From the rated condition of the engine.
The current asymmetry alarm is congured by default (Alarms table, parameter
257) to perform no action (warning).
WATER IN FUEL (CEA7 VER469).
The water in fuel alarm of the CEA7 control unit is associated to the detection of
water in fuel by the control engine electronics and it is notied to the control unit
through J1939 protocol. This alarm is enabled to IVECO and BAUDOUIN engines.
The control unit enables the alarm when control engine electronics detects the
water in fuel condition in a programmable period of time (debounce time) (Alarms
table, parameter 259).
The water in fuel detection is enabled by default (Alarms table, parameter 258)
to be activated: Always.
The water in fuel alarm is congured by default to not take any action (warning).