EasyManua.ls Logo

Hioki 3196 - Page 21

Hioki 3196
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- page 19 -
Next, the waveform of each "wave" event was checked, and 2 types of events were found.
We can assume that the events "switched to a sine wave after the waveform noise" were due to the
switching to the UPS output (stand-by system).
Not switched to a sine wave after the waveform noiseNo.1:
Switched to a sine wave after the waveform noiseNo.2:
It appears that waveform No.1 has a higher noise level and should be switched to the UPS output.
However, waveform No.2 shows a bigger difference in the current waveform when the voltage
waveform shows the noise. Therefore, we can assume that a transient overvoltage occurs
simultaneously when this event occurs. Unfortunately, the transient overvoltage is not detected,
because its threshold is set at 0.480kV (480V).
We propose setting the threshold at 1/2 of the waveform peak (70V= 0.0718kV for 100V circuit)
No.1: Not Switched to the Sine Wave after the Waveform Noise
No.2 Switched to the Sine Wave after the Waveform Noise
Switched to the sine wave

Other manuals for Hioki 3196

Related product manuals