EasyManua.ls Logo

Hioki 3196 - Page 26

Hioki 3196
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Outflow
Outflow
Inflow
Inflow
Inflow
Inflow
Inflow
Inflow
Inflow
Inflow
Inflow
Inflow
- page 24 -
Model 9624 PQA HiVIEW and Model 9624-10 PQA HiVIEW Pro show the harmonic time plot
graph by connecting the maximum and minimum values in each interval with a horizontal line.
Therefore, a rapid change is reflected in the time plot graph.
However, the judgment of inflow and outflow is not easy to make using that time plot graph, so we
recommend converting the data to CSV format and creating a graph with "AvePhasesum" of the
relevant harmonics order only (without using "MaxPhasesum" and "MinPhasesum"), to determine
the inflow and outflow.
Example 1
-180
-90
0
90
180
Time
Phase difference [deg.]
Example 2
Red: 3rd harmonic, Green: 5th harmonic, Blue: 7th harmonic
Date
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
2004/9/3
Time
6:50:00
6:55:00
7:00:00
7:05:00
7:10:00
7:15:00
7:20:00
7:25:00
7:30:00
7:35:00
7:40:00
7:45:00
AvePhasesum (5)
Inflow /
Outflow
-93.07
-90.63
-84.20
-89.23
-87.79
-87.42
-87.16
-86.08
-79.51
-84.34
-80.74
-78.41
Calculation
=IF(ABS(C2)>90,"Outflow",
"Inflow")

Other manuals for Hioki 3196

Related product manuals