1.4 Display elements
LED Color Meaning
System green lights up The transmission rate has been recognized and the
power supply is in order
Signal contact: no signal
red flashes Transmission rate has not yet been recognized
No transmitting bus subscriber present
No connection to a partner repeater sending frames
Send and receive optical fibers have been
transposed.
Transmission rate does not correspond to
PROFIBUS-DP.
Only one active bus subscriber is connected, which
is only sending tokens to itself. The indicator must
switch over after a second bus subscriber has been
activated (token frames on their own are not enough
to set the transfer rate).
The connected RS 485 segment is only terminated
at one end.
Signal contact: no signal
red/green flashes Transmission rate recognized but
the network slot time could not be determined
(network parameter HSA is set too low, no
transmitting bus subscriber present)
one optical port is set to ”Redundant optical ring“
mode, but not the second (this operating mode must
always be set at both optical ports)
the slot time of the network configuration is too short
Signal contact: no signal
none Power supply has failed (total failure). Failure of
both power supply sources with redundant infeed.
Power supply connected incorrectly
Repeater defective
Signal contact: signal
CH1
CH1
CH2
CH4
System
CH1
CH3
System
CH1
CH3
System
CH1CH2CH3CH4