40
Installation OZD Profi 12M ...
Release
01
07/2017
4.3 Setting compatibility
Note: The functional compatibility on OZD Profi 12M ...
a
is switched on or
switched off with the DIP switch S8.
– When operating OZD Profi 12M ...
a
with OZD Profi PRO or with previous
OZD Profi 12M ...
b
the functional compatibility must be switched off
(S8=0). The devices are directly compatible.
– When operating OZD Profi 12M... with OZD Profi G3a, ... G4a, ... G3a-
1300, ... G4a-1300, ... P3a, ... P4a the functional compatibility must be
switched on (S8=1).
Only turn switch S8 to Position 1 if the OZD Profi 12M ...
a
is being used
as a spare or expansion device in existing networks in conjunction with
these devices and a direct optical connection is to be made. The following
tables show the switch assignment:
a. Device variants with 1 or 2 electrical ports (CH1, CH2),
DIP switch: S0 - S8
b. Device variants with 1 electrical port (CH1) only,
DIP switch: S0 - S7