4.4 Setting compatibility, operating mode and transmitting power
17
4 Setting Up
Version 2.4 04/07
4.4 Setting compatibility, operating mode and transmitting power
Please note:
The OZD Profi 12M … must be switched off when
changing the operating mode.
You can switch off the OZD Profi 12M … by, e.g.,
unplugging the 5-pin terminal block.
4.4.1 Setting the compatibility
The DIL switch S7 is used to switch the functional
compatibility to devices of the preceding generation
OZD Profi P3a, … P4a, … G3a, … G4a,… G3a-1300 and
… G4a-1300 either off or on. Default setting at S7 is
Position 0 (compatibility is switched off).
DIL switch S7 (compatibility) in
Position 0:
compatibility to
OZD Profi P3a, OZD Profi P4a,
OZD Profi G3a, OZD Profi G4a,
OZD Profi G3a-1300 and
OZD Profi G4a-1300
switched off
DIL switch S7 (compatibility) in
Position 1:
compatibility to
OZD Profi P3a, OZD Profi P4a,
OZD Profi G3a, OZD Profi G4a,
OZD Profi G3a-1300 and
OZD Profi G4a-1300
switched on
The functional compatibility to OZD Profi modules of
the preceding generation OZD Profi P3a, … P4a, … G3a,
… G4a, … G3a-1300 and … G4a-1300 is switched on
with the DIL switch S7=1.
This operating mode is required when operating this
module together with new devices.
Only turn switch S7 to Position 1 if the OZD Profi 12M …
is being used as a spare or expansion device in existing
networks in conjunction with OZD Profi of the preceding
generation, and a direct optical connection is to be
made.
The following illustrations show the switch assignment of
the OZD Profi 12M … at S7=1 for
as a spare device for as a spare device for
OZD Profi P3a OZD Profi G3a,
and OZD Profi G4a,
OZD Profi P4a OZD Profi G3a-1300
and
OZD Profi G4a-1300