No Setting Item
Seven-segment
digital
display
Setting Options
10
Control on target value of
superheat degree of heat
exchanger of cooling
indoor unit
00 Initial setting
01 Target value+2℃
02 Target value+1℃
03 Target value-1℃
04 Target value-2℃
11
Control on target value of
supercooling degree of the
exchanger of heating
indoor unit
00 Initial setting
01 Target value+6℃
02 Target value+3℃
03 Target value-3℃
04 Target value-6℃
12
Change of EVI max.
aperture of indoor unit
heating OFF
00 Initial setting
01 EVI Max. aperture reduction mode 1
02 EVI Max. aperture reduction mode 2
03 EVI Max. aperture reduction mode 3
04 EVI Max. aperture reduction mode 4
05 EVI Max. aperture reduction mode 5
13
Change of EVI max.
aperture of indoor unit
heating OFF
00 Initial setting
01 EVI Max. aperture reduction mode 1
02 EVI Max. aperture reduction mode 2
14
Control on heating start-up
and general supercooling
degree of indoor unit
00 Initial setting
01 EVI aperture gets larger in general
02 On-startup EVI aperture getting larger mode 1
03 On-startup EVI aperture getting larger mode 2
04 On-startup EVI aperture getting larger mode 3
15
Change of EVI initial
aperture in cooling
operation
00 Initial setting
01 Original set aperture ×0.95
02 Original set aperture ×1.03
03 Original set aperture ×1.05
04 Original set aperture ×1.10
16
Change of EVI initial
aperture in heating
operation
00 Initial setting
01 Original set aperture ×0.95
02 Original set aperture ×1.03
03 Original set aperture ×1.05
04 Original set aperture ×1.10
17 Low noise mode
00 Initial setting
01 Fan speed reduction 1
02 Fan speed reduction 2
03 Fan speed reduction 3
04 Compressor frequency reduction 1
05 Compressor frequency reduction 2
06 Compressor frequency reduction 3
07 Fan speed + compressor frequency reduction 1
08 Fan speed + compressor frequency reduction 2
09 Fan speed + compressor frequency reduction 3
18 DEMAND control
00 Initial setting
01 40% of set value
02 60% of set value
03 70% of set value
04 80% of set value
05 100% of set value