No Setting Item
Seven-segment
digital
display
Settings
19 WAVE control
00 Initial setting
01 40% of set value
02 60% of set value
03 70% of set value
04 80% of set value
20
00 Initial setting
01 Control started at blast temperature of 10℃
02 Control started at blast temperature of 12℃
03 Control started at blast temperature of 14℃
21
00 Initial setting
01 Capacity suppression mode
02 Blast temperature control mode
22 Fan speed adjustment
00 Initial setting
01 Target rotating speed -15rpm
02 Target rotating speed -30rpm
23 No function is available 00
24
01 Initial setting
02 Min. aperture reduction mode 1
03 Min. aperture reduction mode 2
04 Min. aperture reduction mode 3
05 Min. aperture reduction mode 4
06 EVI off
25
No function is available
00
26
No function is available
00
27
Setting of operation of outdoor
unit fan upon setting of Snow
sensor
00
Fan operates continuously upon setting of Snow
sensor
01 Fan operates intermittently (off for 570s/on for 30s)
02 Fan operates intermittently (off for 540s/on for 60s)
03
Fan operates intermittently (off for 480s/on for
120s)
04
Fan operates intermittently (off for 300s/on for
300s)
28
u 1 FF Initial setting
u 2 00 Indoor units with address 00 are set as VIP
u 3 01 Indoor units with address 01 are set as VIP
u 4 ** Indoor units with address ** are set as VIP
u 5 63 Indoor units with address 63 are set as VIP
29
Automatic in-night mute mode
00 Initial setting
01
In-night mute ni setting takes effect, and exit in 8
hours
02
In-night mute ni setting takes effect, and exit in 9
hours
03
In-night mute ni setting takes effect, and exit in 10
hours
30
00 Initial setting
01 High indoor unit head drop setting
High head drop s
etting
VIP function
in indoor unit
(up to 5 units)
Change of EVI min. apertu
r
e
of indoor unit heating OFF
When Externa air
processing unit is connected
Low cooling blast temperature
protection