3. Transportation and Handling
3.1 Transportation
Transporttheproductasclosetotheinstallation
locationaspracticablebeforeunpacking.
3.3 CombinationofSwitch BoxandIndoor
Unit Combinationisasfollows.
Table3.1CombinationofIndoorUnit
3.2 HandlingofSwitch Box
Do not put any foreign material into the indoor
unit and check to ensure that none exists in the
Switch Box before the installation and test run.
Otherwise, a fire or failure, or something similar
may occur.
Do not put any material on the product.
Be careful not to damage insulation materials
of unit’s surface when lifting.
NOTES:
1. Exceedingthetotalcapacitymaycauseinsufficientperformanceandabnormalsound.Besureto
connecttheSwitch Boxwithintheallowabletotalcapacity.
2. Incaseof8HPor10HPtypeindoorunitconnection:
Onlysingleunitperbranchisallowedtobeconnected.
Uptotwo8HPor10HPtypeindoorunitscanbeconnectedtotheSwitch Boxwithinthe
“MaximumTotal CapacityofAllConnectedIndoorUnits”showninabovetable.
Makesuretoincreasethepipeconnectionsizebyusingtheappropriateaccessorypipe.
Model HCHM-N04X HCHM-N08X HCHM-N12X HCHM-N16X
NumberofBranches(forIndoorUnit) 4 8 12 16
SingleUnit
PerBranch
MaximumTotalCapacityof
AllConnectedIndoorUnits
16.0HPorless
(Max.44.8kW)
30.0HPorless
(Max.85.0kW)
30.0HPorless
(Max.85.0kW)
30.0HPorless
(Max.85.0kW)
MaximumTotalCapacityof
ConnectedIndoorUnitsPer
Branch
6.0HPorless
(Max.16.0kW)
6.0HPorless
(Max.16.0kW)
6.0HPorless
(Max.16.0kW)
6.0HPorless
(Max.16.0kW)
MultipleUnits
PerBranch
MaximumNumberof
ConnectedIndoorUnitsPer
Branch
6 6 6 6
MaximumTotalCapacityof
AllConnectedIndoorUnits
16.0HPorless
(Max.44.8kW)
30.0HPorless
(Max.85.0kW)
30.0HPorless
(Max.85.0kW)
30.0HPorless
(Max.85.0kW)
MaximumTotalCapacityof
ConnectedIndoorUnitsPer
Branch
6.0HPorless
(Max.16.0kW)
6.0HPorless
(Max.16.0kW)
6.0HPorless
(Max.16.0kW)
6.0HPorless
(Max.16.0kW)