Hisense HCHM-N04X - Initial Check

Hisense HCHM-N04X
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unit: mm
Service Space
Service Access Door 1 (*)
Electrical Box
( 450)
Service Access Door 3
Min. 300
Upper Side
Bottom Side
Min. A
Min. 100
Min. 500
Min. 100
4-Suspension Bolt
M10 or W3/8
(Field-Supplied)
Service Access Door 2
( 450)
( 450)
100
50
* Service access door 1 is required for models
HCHM-N04X, HCHM-N08X, HCHM-N12Xand HCHM-N16X.
100
100
50
4.2 InitialCheck
InstalltheSwitch Boxwithaproper
clearance arounditformaintenanceworking
space,as showninFigure4.1below.
Size
Model
A
HCHM-N04X Min.100
HCHM-N08X
Min.400
HCHM-N12X
HCHM-N16X
PurposeofEachServiceAccessDoor
Name Purpose
ServiceAccess
Door1
Useduringinspectionofindoorunit
connectingside.
ServiceAccess
Door2
Useduringinspectionofindoorunit
connectingside.
ServiceAccess
Door3
Useduringinspectionofelectrical
componentsinsideelectricalbox.
Figure4.1ServiceSpace
Checktoensurethattheceilingissufficiently
strongtosustaintheSwitch Box.Iftheceiling
is weak,abnormalsoundandvibrationmay
occur.
Whentheelectronicexpansionvalveinthe
Switch Boxisactivated,achangeinthetypical
refrigerantflowsoundsmaybeheardor
perceivedfromtheSwitch Box.Takethe
following actiontominimizethesound.
(A) InstalltheSwitch Boxinsidetheceiling.As
for theceilingmaterial,selectamateriallike
a plasterboardatleast9mm(1inch),which
minimizesoperationsound.
(B) DonotinstalltheSwitch Boxinaplace
near bedroomsorhospitalrooms.
Whentheoperationischangedtocooling/
heatingmode,achangeinthetypicalrefrigerant
flowsoundsmaybeheardorperceivedfromthe
Switch Box.
Therefore,installtheSwitch Boxintheceiling of
thecorridorsothattherefrigerantflowing sound
maynotbeheardintheroom.
DonotinstalltheSwitch Boxinahotor humid
place,suchasakitchen,toprevent
condensationontheoutersurfaceofthe Switch
Box.
WheninstallingtheSwitch Boxinsuchplaces,
applyadditionalinsulation.
Payattentiontothefollowingpointswhenthe
Switch Boxisinstalledinahospitalorother
facility wherethereareelectronicwavesfrom
medical equipment.
(A)
(B)
(C)
DonotinstalltheSwitch Boxwherethe
electromagneticwaveisdirectlyradiatedto
theelectricalboxorcommunicationcable.
Ensuretheinstallationplaceisconvenient
fortherefrigerantpipingorelectricalwiring
connection.
Donotdrill,ordrivescrewsintothecabinet. Use
onlymountingpointsprovided.
IncasetheSwitch Boxisrequiredtomovefrom
the ceiling,prepareanotherserviceaccessdoor.
InstalltheSwitch Boxandcomponentsas
far aspracticableoratleast3m(10ft)
fromthe electromagneticwaveradiator.
Installanoisefilterwhenthepowersupply
emitsharmfulnoises.
8