Item Mark
AllowablePiping
Length
Piping
Length
MaximumPipingLengthbetweenBRANCH PIPEof1st
BranchandTerminalIndoorUnit
L2 ≤90m(295ft)
1
MaximumPipingLengthbetweenSwitch BoxandIndoorUnit
L3a,a+b+d,
a+b+eora+c
≤40m(131ft)
2
InCasethereisBranchafterSwitch Box, TotalPiping
LengthfromSwitch BoxtoEachConnectedIndoor
UnitperBranch
a+b+c+d+e ≤40m(131ft)
Height
Difference
InCasethereisBranchafterSwitch Box ,
HeightDifferencebetweenIndoorUnitsConnectedto
SameConnectionPortof
Switch Box
H3 <4m(13ft)
HeightDifferencebetweenSwitch Boxes
H4 <15m(49ft)
HeightDifferencebetweenSwitch Box
andIndoorUnit
H5 RefertoNOTE3.
㹟
㹡
㹠
L3a L3a
L3a
L3a
L2
H4
H3
d
e
Switch Box
Switch Box
Switch Box
Indoor
Unit
: 3 Pipes (High/Low Pressure Gas Pipe, Low Pressure Gas Pipe and Liquid Pipe)
: 2 Pipes (Gas Pipe and Liquid Pipe)
H5
H5
H5
BRANCH PIPE
(2) PipingWorkforSwitch Box
Refrigerantpipingsizedependsonthecombinationswiththeoutdoorunit.Refertotheinstallation
andmaintenancemanualfortheoutdoorunit.PerformpipingworkfortheSwitch Boxaccordingto
the followingfigure.
NOTES:
1. Whenthepipinglengthfromthefirstbranchtotheterminalindoorunitexceeds40m (131 ft), there
are restrictions.Refertotheinstallationandmaintenancemanualfortheoutdoorunit.
2. Ifthepipinglength(L3a)betweeneachSwitch Boxandindoorunitisconsiderablylongerthanother
indoor unit,refrigerantmaynotflowwell,andmaylessentheunit’sperformancecomparedtoother
models.(RecommendedPipingLength:Within15m(49ft))
3. WhentheheightdifferencebetweenSwitch Boxandindoorunitislong,theperformancemay
decrease.(RecommendedPipingLength:Within15m(49ft))
Each Water Module must occupy one branch of Switch Box exclusively.
4.
or Water Module
Indoor
Unit
or Water Module
Indoor
Unit
or Water Module
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit