15. Power Saving Details Setting
A16381TMF2
33
NOTES:
•
Indoor rotation control cannot be set for the sub remote controller.
•
If the "Power Savings Mode" changes the "Power Saving Details Setting" in outdoor capacity control, the
"Power Saving ON/OFF" turns OFF.
•
This function can be used only when the operation mode is cooling/heating.
•
The cooling/heating capacity can decrease when using the "Power Saving" function.
(3) Intermittent Control Setting
Item Description
Level Change The power saving details settings can change the power savings level.
1. Set Intermittent Control
Step1. Select "Service Menu" on the Service & Installation screen
and press "OK".
Step2. Select "Power Saving Details Setting" and press "OK.
→ Power Saving Details Setting screen is displayed.
Step3. Select "Intermittent Control" and press "OK".
Step4. Change level
Press " " or " " to select the level and press "OK".
It changes as follows:
"Low
<->
Med
<->
High"
↔
"Low only"
↔
"Med only"
↔
"High only".
Press " " to return to Step3.
Power Saving Details Setting
Intermittent Control
Reset Default
Rotation Control
Capacity Control
OK
Select Back
Intermittent Control
Low only
Med only
High only
Select setting range of power savings.
OK
Select Back
Low <-> Med <-> High
NOTES:
•
This function cannot be set when only the total heat exchanger is connected.
•
Each power savings level repeats the operation as follows:
Cool/Dry Mode Heat Mode
Power Saving : LOW Normal Mode 20 minutes ⇔ Fan Mode 10 minutes Normal Mode 25 minutes ⇔ Fan Mode 5 minutes
Power Saving : MED Normal Mode 17 minutes ⇔ Fan Mode 13 minutes Normal Mode 20 minutes ⇔ Fan Mode 10 minutes
Power Saving : HIGH Normal Mode 15 minutes ⇔ Fan Mode 15 minutes Normal Mode 15 minutes ⇔ Fan Mode 15 minutes
•
If the "Power Savings Mode" changes the "Power Saving Details Setting" in intermittent control, the "Power
Saving ON/OFF" turns OFF.
•
The cooling/heating capacity can decrease when using the "Power Saving" function.
(4) Reset Method
1. Reset power saving details setting to default values
Step1. Select "Service Menu" on the Service & Installation screen
and press "OK".
Step2. Select "Power Saving Details Setting" and press "OK.
Step3. Select "Reset Default" and press "OK".
Step4. Select "Yes" and press "OK", reset the power saving details
to default and return to Step2.
Select "Cancel" and press "OK", return to Step2.
Step6. Change the Fan Mode Time
Select "Fan Mode Time" and press "OK".
Press " " or " " to set the fan mode time. Press "OK" to
confirm the setting.
It changes as follows:
"10 min"
↔
"5 min"
↔
"3 min".
Press " " to return to Step4.
Rotation Control
OK
Select Back
5 min
3 min
10 min
Select time in fan mode per 1 unit.
Power Saving Details Setting
Intermittent Control
Reset Default
Rotation Control
Capacity Control
Reset to default value for Power
Saving Details setting?
Yes Cancel
OK
Select Back
OK