Setting Defrosting Inhibit Period
DFTIM_OT P5
DFTIM_OT P0
DFTIM_OTP 10
Time
Outdoor temperature
– 1 0 – 5˚C 0 ˚C
Notes:
(1) The first inhibit time after operation start is set to DFTIM_FST.
(2) From the second time onwards, the inhibit time is set according to the time required for
defrosting.
Reverse cycle operation time [DEFCOL] : DEFTIM_COL is set.
Reverse cycle operation time < [DEFCOL] : The time corresponding to outdoor tempera-
ture is set.
9
STARCPIL
i
i i
(1)
(2)
(3)
(4)
(5) Outdoor fan speed :
(6) Compressor start control : Same as Basic Heating operation
(7) Compressor speed :
(8)
}
Same as Basic
Heating operation
55