Hitachi RAS-10JH4 - Checking Outdoor Unit Electrical Parts; OH Thermistor Temperature Rise; Overload Lower Limit Cut; Failure of Switching

Hitachi RAS-10JH4
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication error.
LD301 blinks 9 times.
Is the connecting cable
connected properly?
(Is 35V being output on the
indoor unit side?)
Are CN3 and CN4
connected?
Is DC35V being output
between terminals C and D?
Normal: DC32V – 39V
Standby: DC18V – 23V
Is DC35V being output at
both ends of R35?
Connect CN 3 and CN4.
Connect properly.
Replace the power P.W.B.
• Defective SW power supply.
Replace the power P.W.B.
• NF coils, IF coils, etc.
may be broken.
Check the interface circuit
and replace the main
P.W.B. if needed.
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
- 94 -