12.Timer lamp blinking:blinking 11 times
<Situation> Electric dust collector(High coltage generator)is not operating.
<Cautions>
·This failune modes can be redisplayed by remote controller.Please refer to
「Self-diagnosis memory function」.
·Do not touch the electric dust collector electrodes while the power supply is on.
<Estimated failure locations> ·
High voltage generator or its electrode out of order.
·
High voltage generator electrode dirtied.
·CN14 connector is loose、lead wire break.
– 13 0 –
No
Yes
Yes
No
Clean the electrodes.
Correct the connector.
Is the CN14 connector loose?
Or is there a wire break?
Replace the electric dust collector(High voltage generator).
<Diagonsis flow>
Initiating troubleshooting
Are the high voltage generator electrodes dirty?