9 DRAIN PIPING
9.1 DRAIN DISCHARGING BOSS
When the base of the outdoor unit is temporarily utilized as a
drain receiver and the drain water in it is discharged, this drain
boss is utilized to connect the drain piping.
Model Applicable Model
DBS-12L
RAS-(2/2.5)HVNP1
RAS-3HVNC1
RAS-3HVRNS3
Connecting procedure
1 Insert the plastic cap into the drain boss up to the extruded
portions.
2 Insert the boss into the unit base up to the extruded portions.
3 Size of the drain boss is 15 mm (O.D.)
4 A drain pipe should be eld-supplied.
? NOTE
• Donotusethisdrainbosssetinacoldarea,becausethedrainwater
mayfreeze.
• This drain boss is not sufcient to collect all the drain water. If
collectingdrainwateriscompletelyrequired,provideadrain-panthat
isbiggerthantheunitbaseandinstallitundertheunitwithdrainage.
Drain pipe
Plastic cap
Plastic cap
Drain hole
100 mm
Plastic cap
Drain hole
Push Push
≥ O.D. 16 mm
10 ELECTRIC WIRING
10.1 GENERAL CHECK
1 Ensure that the eld-supplied electrical components (mains
power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the
electrical data indicated. Make sure that they comply with
national and regional electrical codes.
2 Following the Council Directive 2004/108/EC(89/336/EEC),
relating to electromagnetic compatibility, next table indicates:
Maximum permissible system impedance Z
max
at the
interface point of the user’s supply, in accordance with
EN61000-3-11
MODEL Z
max
(Ω) MODEL Z
max
(Ω)
RAS-2HVNP1 - RAS-3HVNC1 -
RAS-2.5HVNP1 - RAS-3HVRNS3 -
3 Harmonics situation of each model regarding IEC 61000-3-2
and IEC 61000-3-12 is as follows:
MODELS SITUATION REGARDING
IEC 61000-3-2 AND IEC 61000-3-12 Ssc “xx”
MODELS
Equipment complying with IEC 61000-3-2
(professional use)
RAS-2HVNP1
RAS-2.5HVNP1
RAS-3HVNC1
RAS-3HVRNS3
4 Check to ensure that the power supply voltage is within +/-
10% of the rated voltage.
5 Check to ensure that power supply has an impedance low
enough to warranty not reduce the starting voltage more
than 85% of the rated voltage.
6 Check to ensure that the ground wire is connected.
7 Connect a fuse of specied capacity.
? NOTE
Checkandtesttoensurethatifthereismorethanonesourceofpower
supply,thatallareturnedOFF.
! CAUTION
• Checktoensurethatscrewsforterminalblockaretightlytightened.
• Checktoensurethattheindoorfanandtheoutdoorfanhavestopped
beforeelectricalwiringworkorperiodicalcheckisperformed.
• Protectthewires,drainpipe,electricalparts,fromratsorothersmall
animals.Ifnotprotected,ratsmaydamageunprotectedparts,andat
theworst,arewilloccur.
• Wrapthe accessorypackingaroundthewires,and plug thewiring
connectionholewiththesealmaterialtoprotecttheproductfromany
condensedwaterandinsects.
• Tightlysecurethewireswiththecordclampinsidetheindoorunit.
• Lead the wires through the knockout hole in the side cover when
usingconduit.
• Securethecable of theremotecontrol switch withthe cord clamp
insidetheelectricalbox.
• Electricalwiringmustcomplywithnationalandlocalcodes.Contact
yourlocalauthorityinregardstostandards,rules,regulations,etc.
• Checkthatthegroundwireissecurelyconnected.
• Connectafuseofspeciedcapacity.
! DANGER
• Donotconnectofadjustanywiringorconnectionsunlessthe
mainpowerswitchisOFF.
• Check that the earth wire is securely connected, tagged and
lockedinaccordancewithnationalandlocalcodes.
DRAIN PIPING
PMML0398B rev.0 - 11/2015 - P5416651
11