13 UNITS INSTALLATION
13.1 OUTDOOR UNITS INSTALLATION
CAUTION
• Transport the products as close to the installation location as
practical before unpacking.
• Do not put any material on the products.
• Apply four lifting wires on to the outdoor, when lifting it by crane.
CAUTION
• Install the outdoor unit with sufcient clearance around it for
operation and maintenance as shown in the next gures.
Install the outdoor unit where good ventilation is available
• Do not install the outdoor unit where is a high level of oil mist,
salty air or sulphurous atmosphere.
• Install the outdoor unit as far as practical (being at least 3
meters) from electromagnetic wave radiator (such as medical
equipment).
• For cleaning, use noninammable and nontoxic cleaning li-
quid. Use of inammable agent may cause explosion or re.
• Work with sufcient ventilation, since working in an enclosed
space may cause oxygen deciency. Toxic gas may be pro-
duced when cleaning agent is heated to high temperature by,
e.g., being exposed to re.
• Cleaning liquid shall be collected after cleaning.
• Pay attention not to clamp cables when attaching the service
cover to avoid electric shock or re.
CAUTION
• Keep clearance between the units of more than 50mm, and
avoid obstacles that may hamper air intake, when installing
more than one units together.
• Install the outdoor unit in the shade or not exposed to direct
sunshine or direct radiation from high temperature heat source.
• Do not install the outdoor unit in a space where a seasonal
wind directly blows to the outdoor fan.
• Check to ensure that the foundation is at, level and suf-
ciently strong.
• Install the unit in a restricted area not accessible by the ge-
neral public
• Aluminum ns have very sharp edges. Pay attention to the
ns to avoid injury.
13