63
FORCED COOLING
In order to accumulate refrigerant, units operate in cooling cycle.
Execution condition and operation status are shown below.
[Execution condition]
With neither indoor unit 1 and 2 not operated, when forced cooling switch is turned ON, forced cooling will
be performed.
Always operation status of indoor unit are monitored and forced cooling is inhibited when operation of any
unit is detected.
[Operation status]
Outdoor unit fan: Fixed in LO.
Compressor rotation speed: Fixed in 3900min
-1
.
[Note]
During forced cooling, if failure occurs in outdoor unit, thermostat is turned off. However, it is not counted.
Since rotation speed of compressor is fixed in 3900min
-1
during forced cooling, compressor fixed speed
control at start is not performed.
The following shows the operation state of forced cooling.
Power
Power
In-rush Prevention
Approx 100ms
31.25PPS
Hold 500ms
Hold 500ms
Initialization finished
TSKTM1
3900rpm
Balancing period 3min.
15sec. + sub
80sec.
100ms
Service switch
Heating output
Cooling output
Outdoor fan
Turns on
for Heating
Operation
Unit 1
Unit 2
Unit 1
Compressor
rotation speed
Main microcomputer
Electric expansion valve
Power relay
Compressor
Reversing
valve
Unit 2
1sec
1sec
1sec
Lo
Forced cooling request Balancing request
Forced cooling request Balancing request
520
480
0
520
480
0
[Outdoor temperature<40°C]
[Outdoor temperature<40°C]
PSTART
PSTART
<TD control + 3N compensation + Diving control>
<TD control + 3N compensation + Diving control>
TSKTM1 and PSTART are EEPROM data.