3 Piping work and
refrigerant charge
75
SMGB0087 rev.0 - 12/2013
3
3.3.3 Piping system for line branch
OU 3HP 4HP 5HP 6HP 8HP 10HP 12HP
IUquantityallowed
IVXPremium 2 -3 2 - 5 2 - 6 2 - 8
IVXStandard -- 2 - 4
(picture is as example)
Maximum refrigerant piping length (Line branch system)
IVX Premium series
(m)
OutdoorUnit 3HP 4HP 5HP 6HP 8HP 10HP 12HP
Maximumpipinglengthbetweenthe
outdoorunitandthefarthestindoor
unit
ActualLength(L1) 50 75 100
EquivalentLength(EL) 70 95 125
Maximumpipinglengthfromrstbranchtoeachindoorunit(L2) 20 30 40
Maximumpipinglengthfrombranchtoindoorunit(L3) 10 15
TotalpipinglengthL4+(L31+L32+L33....) 60 95 100 145
MaximumheightdifferenceOutdoor/Indoor(H)
(OutdoorUnitisHigher/Lower.)
30 / 20
MaximumheightDifferenceIndoor/Indoor 10
Maximumheightdifference:
Branchpipe/Indoor
Branchpipe/branchpipe
3
IVX Standard series
(m)
OutdoorUnit 4HP 5HP 6HP 8HP 10HP 12HP
Maximum piping length between the outdo-
or unit and the farthest indoor unit
Actual Length (L1) 70 75 100
Equivalent Length (EL) 90 95 125
Maximum piping length from rst branch to each indoor unit (L2) 20 25
Maximum piping length from branch to indoor unit (L3) 10 15
Total piping length L4 + (L31+L32+L33....) 70 75 100 145
Maximum height difference Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower)
30 / 20
Maximum height Difference Indoor / Indoor 3
Maximum height difference:
Branch pipe/Indoor
Branch pipe/branch pipe
3