8  REMOTE CONTROLLER OPERATION
It is advisable to use PC-ART or PC-ARF remote controller (both optional). For more information about it installation and operation, 
please refer to its corresponding Installation and Operation Manuals.
7
7  BEFORE OPERATION
  CAUTION
•  Supply  electrical  power  to  the  system  for  approximately  12 
hours before start-up or a long shutdown. Do not start the 
system immediately after power supply, it may cause a com-
pressor failure because the compressor is not heated well.
•  When the system is started after a shutdown longer that ap-
proximately 3 months, it is recommended to check the system 
by your service contractor.
•  Turn OFF the main switch when the system is to be stopped 
for a long period of time: If the main switch is not turned OFF, 
electricity will be used, because the oil heater is always ener-
gised during compressor stopping.
•  Make sure that the outdoor unit is not covered with snow or 
ice. If covered, remove it by using hot water (approximately 
50°C). If the water temperature is higher that 50°C, it will cau-
se damage to plastic parts.
9  AUTOMATIC CONTROLS
The system is equipped with the following functions.
 
Three minute guard
The compressor remains off for at least 3 minutes once it has stop-
ped. If the system is started within approximately 3 minutes after it 
has stopped, the RUN indicator is activated. However, the cooling 
operation or the heating operation remains off and does not start 
until after 3 minutes has elapsed.
Operation may stop for 6 minutes maximum to protect compressor.
 
Frost prevention during cooling operation
When the system is operated in a low temperature room, the coo-
ling  operation  may  be  changed  to  fan  operation  for  a  while  to 
avoid frost formation on the indoor heat exchanger.
 
Automatic restart after power failure
If the power supply is interrupted for short periods of time (up to 
2 seconds) the Remote Control switch will retain the settings and 
the unit will restart when the power is restored.
If Automatic Restart is required after periods of lost power supply 
in excess of 2 seconds please contact your distributor (optional 
function).
 
Slow air control during heating operation
When the compressor is stopped while the thermostat is OFF, or 
the system is performing the automatic defrosting operation, the 
fan speed is set at the slow position.
 
Automatic defrosting cycle
When the heating operation is stopped by pressing RUN/STOP 
switch, frosting on the outdoor unit is checked and the defrosting 
operation may be performed for the maximum of 10 minutes.
 
Prevention of overload operation
When the outdoor temperature is too high during heating opera-
tion, heating operation is stopped due to activation of the outdoor 
thermistor until the temperature becomes low.
 
Hot start during heating operation
To  prevent  cold air discharge, the fan speed  is  controlled  from 
the slow position to the set position according to the discharge air 
temperature. At this time the lover is xes horizontally.