Refrigerant piping & refrigerant charge
14.2 PIPING CONNECTION FOR OUTDOOR UNIT
1  Take the piping cover away from the unit. Then fetch the pipes 
through the rear side and route piping according to the ins-
tallation place as shown in the gure. Make holes by cutting 
along the guideline at the rear of the cover or punching with 
a driver. Remove the burr with a cutter, and place a insulation 
(eld supplied) to protect cables and pipes.
Pipe cover
Rear side 
piping
Stop valve
Direction to remove pipe cover
Connec
-
ting piping
2  Attach the pipe cover in order to prevent rainwater from ente-
ring inside the cabinet.
3  Use  a  pipe  bender  for  pipe  bending  work  when  connecting 
pipes.
4  Check to ensure that the stop valves are completely closed 
before connecting pipes.
5  Connect the eld supplied refrigerant pipes to the indoor unit 
and outdoor unit. Apply the oil thinly at the seat are nut and 
pipe before tightening.
  The required tightening torque is as follows:
Pipe Size Tightening Torque (Nm)
Ø 6.35 mm (1/4) 14-18
Ø 9.52 mm (3/8) 34-42
Ø 12.70 mm (1/2) 49-61
Ø 15.88 mm (5/8) 68-82
Ø 19.05 mm (3/4) 100-120
Use two spanners 
here for pipe con-
nection
Do not work with 
two spanners 
here. 
Refrigerant 
 
leakage shall 
occur
6  After connecting the refrigerant piping, seal the open space 
between knockout hole and refrigerant pipes by using insula-
tion material.
Unit 
Side
Nº Description
Insulation Material
Insulation Material
Field Supplied
Insulation Material
7  Operation of stop valve should be performed according to the 
gure below.
8  Close before shipment
14.2.1  Outdoor unit stop valve
Operation  of  stop  valve  should  be  performed  according  to  the 
gures and tables below:
Spindle Type
Stop valve (liquid)
Stop valve (gas)
 Spindle valve 
 Flare nut 
 Cap 
 Check joint for service port
Outdoor unit
Tightening Torque (Nm)
   
Gas 
valve
Liquid 
valve
Gas 
valve
Liquid 
valve
Gas 
valve
Liquid 
valve
Gas 
valve
Liquid 
valve
RAS-(2-2.5)HVNP1 7-9 7-9 34-42 34-42 33-42 33-42 14-18 14-18
RAS-3HVNC1 9-11 7-9 68-82 34-42 33-42 33-42 14-18 14-18
RAS-3HVRNS3 9-11 7-9 68-82 34-42 33-42 33-42 14-18 14-18
Refrigerant 
pressure
Closed before shipment
Refrigerant piping
Hexagonal  wrench 
(eld supplied) (*)
Spindle valve
 
Tighten the spindle with a torque above: 
Counterclockwise…. Open 
Clockwise …. Close
Check joint
 
(Only charging hose can  
be connected) 
Tighten the cap with 16 N.m torque.
Cap
 
Tighten the cap with 37 N.m torque 
(Attach this after work)
14