ENGLISH
16.3.4  DIP switch setting for multiple H-LINK system
The DIP switches of all the outdoor and indoor units have to be set as follows:
Unit Name of DIP switch Mark
Setting before the  
shipment
Function
Outdoor unit
Terminal resistance  DSW5
 
DSW5-1 is “ON” position before shipment.
•  It  is  not  necessary  to  set  when  H-LINK  is  connected  with 
only one outdoor unit.
•  When H-LINK is connected with more than one outdoor unit, 
set as follows:
 - First outdoor unit: Keep DSW5-1 in “ON”.
 - Other outdoor units: Set DSW5-1 to “OFF”.
Refrigerant cycle
DSW4 
RSW1
For setting the refrigerant cycle address of the outdoor unit. Set 
the DSW4 and RSW1 to overlap the setting of other outdoor 
units in the same H-LINK system.
Indoor unit
Refrigerant cycle
DSW5 
RSW2
DSW5
For setting the refrigerant cycle address of the indoor unit. Set 
the DSW5 and RSW2 corresponding to the address of outdoor 
unit in the same refrigerant cycle.
Address of the  
indoor unit
DSW6 
RSW1
DSW6
Setting indoor unit address. Set the DSW6 and RSW1 not to 
overlap the setting of other indoor units in the same refrigerant 
cycle. (If no set, the automatic address function is performed.)
16
Example of the setting of the DIP switches.
(00) (01)
(02)
(00) (00) (00) (00) (01) (01)
(02)
(02) (02)
(00) (01) (02) (03) (00) (01)
(00)
(01) (02)
Indoor 
units
Outdoor 
units
Cycle number 0
Cycle number 1
Cycle number 2
DSW5
Terminal resistance
DSW4
Number of refrigerant cycle. 
(setting for tenth digit
)
RSW1
Number of refrigerant cycle  
(setting for last digit)
DSW6
Address of the indoor unit 
(setting for the tenth digit)
.
DSW5
Number of refrigerant cycle.  
(setting for tenth digit)
RSW2
Number of refrigerant cycle 
(setting for last digit)
RSW1
Address of the indoor unit 
(setting for the last digit)